Ph: +95 1 521101

MCCB (HGM Type): 30 - 250 AF

Things in Common

Rated Insulation Voltage, Ui 1,000 V
Rated Operational Voltage, Ue 690 V
Impulse Withstand Voltage, Uimp 8 kV
Protection Function Overload, short-circuit and instantaneous protection
Suitability for Isolation Yes
Utilization Category A
Pollution Degree 3
Reference Standard IEC 60947-2

 

ModelHGM30HGM50HGM60HGM100HGM125HGM160HGM250
Frame (AF)3050Model63100125160250
Pole (P)2, 3, 41)2, 3, 41)2, 3, 41)2, 3, 41)2, 3, 41)2, 3, 41)2, 3, 41)
Rated Current, at 40° C (A)16, 20, 25, 32Bolt Type16, 20, 25, 32, 40, 5016, 20, 25, 32, 40, 50, 6316, 20, 25, 32, 40, 50, 63, 75, 80, 10016, 20, 25, 32, 40, 50, 63, 75, 80, 100, 125100, 125, 150, 160100, 125, 150, 160, 175, 200, 225, 250
Rated Short-Circuit Breaking Capacity [Icu] (kA rms)Recognition code for orderESESHLESHLESHLESHLESHLESHL
AC660/690 V2.552.558102.557.582.557.5857.58107.588107.58810
AC480/500 V7.5107.51026357.51014267.5101426101426351420263514202635
AC440/460 V1620162038551620263016202630202638552026385520263855
AC380/415 V1620162038551620263016202630202638552026385520263855
AC220/240 V35503550851003550505035505050506585100506585100506585100
DC250 V (2P)510510203051015155101515101520301015203010152030
Service Breaking Capacity
[Ics = % Icu]
10010010010010010010010075501001007550100100100100100100100100100100100100
Endurance
(Durability)
Mechanical30,00030,00030,00030,00030,000#colspan#`25,00025,000
Electrical30,00030,00030,00010,00010,00010,00010,000
Trip Device
Thermal
Magnetic
Long Time [LT]Fixed(1.0) x In(1.0) x In(1.0) x In(1.0) x In(1.0) x In(1.0) x In(1.0) x In
Adjustable(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In(0.8 - 0.9 - 1.0) x In
Instantaneous [INST]400 A 16 - 32 A: 400 A, 40 - 50 A: 10 x In16 - 32 A: 400 A, 40 - 63 A: 10 x In16 - 32 A: 400 A, 40 - 100 A: 10 x In16 - 32 A: 400 A, 40 - 125 A: 10 x In10 x In10 x In
Accessory
InternalAuxilliary Switch AUX
Alarm Switch ALT
Shunt Trip SHT
Undervoltage Trip UVT
ExternalRotary HandleFront Contact TFG
Extended TFH
Motor Operator MOT
Mechanical Interlock MIF`●
Locking Device PLD`#colspan#
Plug-inTDM (LINE/ LOAD)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)
TDM (LINE only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)
TDF (LINE only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)--
TDA (1 row)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)● (3P Only)--
TDA (2 row)● (2, 3P Only)● (2, 3P Only)● (3P Only)● (2, 3P Only)● (2, 3P Only)● (2, 3P Only)--
Cage Terminal Block CTB
Insulation Terminal Cover TCF
Insulation Barrier TQQ
Terminal Extentions TBB-----
Installation and Dimensions
Connection/ InstallationFront ConnectionTerminal Screw
Rear ConnectionHorizontal/ Vertical
Plug-inSwitchboard Type (Line & Load Only), Distribution Board Type2)
DIN Rail InstallationPossible for Using DIN Rail Adapter-Possible for Using DIN Rail AdapterPossible for Using DIN Rail Adapter---
Dimensions (mm)a (2/ 3/ 4P)50/ 75/ 10050/ 75/ 10060/ 90/ 12050/ 75/ 10050/ 75/ 10060/ 90/ 120105/ 105/ 140105/ 105/ 140
b130130155130130155165165
c6868686868686868
Weight (kg)2/ 3/ 4P0.6/ 0.8/ 1.00.6/ 0.8/ 1.00.8/ 1.0/ 1.30.6/ 0.8/ 1.00.6/ 0.8/ 1.00.8/ 1.0/ 1.31.1/ 1.3/ 1.71.1/ 1.3/ 1.7
Detailed Rating and Select122 Page
Characteristics Curve and Outside View70-80 Page

 

1) 4 pole arrangement: Basic specification is R-S-T-N (N-R-S-T is optional).
2) Plug-in: Applicable only 3P.
3) 2P product is just removed versus central pole of 3P product. So, 2P product's dimension is equal to 3P product's dimension.