Technical Particulars
Item | Description | Unit | Required |
---|---|---|---|
1. | Manufacturer/ Country | - | Vietnam Electric Cable Corporation/ Vietnam |
2. | Rated Voltage | kV | 0.6/ 1 |
3. | Standard | - | AS 3560, IEC 60228 |
4. | Voltage Rating | kV | 0.6/1 |
5. | Material of Conductor | - | Aluminium |
6. | Type of Conductor | - | Circular Compacted |
7. | Number of Wires | Wire | |
LV-ABC 4 x 25 | 7 | ||
LV-ABC 4 x 35 | 7 | ||
LV-ABC 4 x 50 | 7 | ||
LV-ABC 4 x 70 | 19 | ||
LV-ABC 4 x 95 | 19 | ||
LV-ABC 4 x 120 | 19 | ||
LV-ABC 4 x 150 | 19 | ||
8. | Diameter of Wires | mm | |
LV-ABC 4 x 25 | 2.17 | ||
LV-ABC 4 x 35 | 2.56 | ||
LV-ABC 4 x 50 | 2.99 | ||
LV-ABC 4 x 70 | 2.17 | ||
LV-ABC 4 x 95 | 2.56 | ||
LV-ABC 4 x 120 | 2.87 | ||
LV-ABC 4 x 150 | 3.20 | ||
9. | Material of Insulation (Phase & Neutral) | - | Black XLPE |
10. | Minimum Insulation Thickness | mm | |
LV-ABC 4 x 25 | 1.07 | ||
LV-ABC 4 x 35 | 1.07 | ||
LV-ABC 4 x 50 | 1.25 | ||
LV-ABC 4 x 70 | 1.25 | ||
LV-ABC 4 x 95 | 1.43 | ||
LV-ABC 4 x 120 | 1.43 | ||
LV-ABC 4 x 150 | 1.43 | ||
11. | Nominal Insulation Thickness: | mm | |
LV-ABC 4 x 25 | 1.3 | ||
LV-ABC 4 x 35 | 1.3 | ||
LV-ABC 4 x 50 | 1.5 | ||
LV-ABC 4 x 70 | 1.5 | ||
LV-ABC 4 x 95 | 1.7 | ||
LV-ABC 4 x 120 | 1.7 | ||
LV-ABC 4 x 150 | 1.7 | ||
12. | Maximum Insulation Thickness: | mm | |
LV-ABC 4 x 25 | 1.9 | ||
LV-ABC 4 x 35 | 1.9 | ||
LV-ABC 4 x 50 | 2.1 | ||
LV-ABC 4 x 70 | 2.1 | ||
LV-ABC 4 x 95 | 2.3 | ||
LV-ABC 4 x 120 | 2.3 | ||
LV-ABC 4 x 150 | 2.3 | ||
13. | Identification of Cores | - | By Ribs or Color Stripes |
14. | Maximum Diameter of Core (Excluding Ribs): | mm | |
LV-ABC 4 x 25 | 9.2 | ||
LV-ABC 4 x 35 | 10.3 | ||
LV-ABC 4 x 50 | 11.9 | ||
LV-ABC 4 x 70 | 13.6 | ||
LV-ABC 4 x 95 | 15.9 | ||
LV-ABC 4 x 120 | 17.5 | ||
LV-ABC 4 x 150 | 18.9 | ||
15. | Maximum Diameter of Completed Cable: | mm | |
LV-ABC 4 x 25 | 22.2 | ||
LV-ABC 4 x 35 | 24.9 | ||
LV-ABC 4 x 50 | 28.7 | ||
LV-ABC 4 x 70 | 32.8 | ||
LV-ABC 4 x 95 | 38.4 | ||
LV-ABC 4 x 120 | 42.2 | ||
LV-ABC 4 x 150 | 25.6 | ||
16. | Nominal Weight of Completed Cable | kg/km | (Approximate) |
LV-ABC 4 x 25 | 400 | ||
LV-ABC 4 x 35 | 529 | ||
LV-ABC 4 x 50 | 721 | ||
LV-ABC 4 x 70 | 981 | ||
LV-ABC 4 x 95 | 1348 | ||
LV-ABC 4 x 120 | 1628 | ||
LV-ABC 4 x 150 | 2074 | ||
17. | Minimum Conductor Breaking Load After Stranding | kN | |
LV-ABC 4 x 25 | 3.5 | ||
LV-ABC 4 x 35 | 4.9 | ||
LV-ABC 4 x 50 | 7.0 | ||
LV-ABC 4 x 70 | 9.8 | ||
LV-ABC 4 x 95 | 13.3 | ||
LV-ABC 4 x 120 | 16.8 | ||
LV-ABC 4 x 150 | 21.0 | ||
18. | Minimum Breaking Load of Cable: | kB | |
LV-ABC 4 x 25 | 14.0 | ||
LV-ABC 4 x 35 | 19.6 | ||
LV-ABC 4 x 50 | 28.0 | ||
LV-ABC 4 x 70 | 39.2 | ||
LV-ABC 4 x 95 | 53.2 | ||
LV-ABC 4 x 120 | 67.2 | ||
LV-ABC 4 x 150 | 84 | ||
19. | Maximum DC Resistance of Conductor at 20°C: | Ω/km | |
LV-ABC 4 x 25 | 1.20 | ||
LV-ABC 4 x 35 | 0.868 | ||
LV-ABC 4 x 50 | 0.641 | ||
LV-ABC 4 x 70 | 0.443 | ||
LV-ABC 4 x 95 | 0.320 | ||
LV-ABC 4 x 120 | 0.253 | ||
LV-ABC 4 x 150 | 0.206 | ||
20. | Maximum AC Resistance of Conductor at 80°C: | Ω/km | |
LV-ABC 4 x 25 | 1.49 | ||
LV-ABC 4 x 35 | 1.08 | ||
LV-ABC 4 x 50 | 0.796 | ||
LV-ABC 4 x 70 | 0.551 | ||
LV-ABC 4 x 95 | 0.398 | ||
LV-ABC 4 x 120 | 0.315 | ||
LV-ABC 4 x 150 | 0.257 | ||
21. | Current Rating at 30°C Ambient | A | (In Free Air) |
LV-ABC 4 x 25 | 105 | ||
LV-ABC 4 x 35 | 125 | ||
LV-ABC 4 x 50 | 150 | ||
LV-ABC 4 x 70 | 185 | ||
LV-ABC 4 x 95 | 225 | ||
LV-ABC 4 x 120 | 260 | ||
LV-ABC 4 x 150 | 285 | ||
22. | Maximum Conductor Temperature/ Normal Operation | °C | 80 |
23. | Maximum Conductor Temperature/ Short Circuit Operation (5s) | °C | 250 |